Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 1 Year |
Still deciding? Get samples of US$ 1500/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | A220/24-60M1 | A220/24-180M3 | A220/24-240M4 | A220/24-360M6 | |
Configuration | 1pcs 24V/60A module +1pcs monitor |
3pcs 24V/60A module +1pcs monitor |
4pcs 24V/60A module +1pcs monitor |
6pcs 24V/60A module +1pcs monitor |
|
Environmental | Operating temperature | -40°C ~ 55°C | |||
Storage temperature | -40°C ~ 70°C | ||||
Relative humidity | 5%~95%RH(40±2ºC,no condensation) | ||||
Atmospheric pressure | 62kPa~106kPa | ||||
Altitude | ≤ 2000m (derating is necessary above 2,000m) | ||||
AC Input | AC input system | L+N+PE/220Vac | |||
Input voltage range | 90VAC ~ 290VAC | ||||
Input AC voltage frequency | 45Hz ~ 65Hz | ||||
THD | <5% (@230Vac,full load) | ||||
Power factor | ≥ 0.99 | ||||
DC Output | Rated output voltage | 24VDC | |||
Adjustable output voltage | 20VDC-30VDC continuously adjustable | ||||
System output current | 60A | 180A | 240A | 360A | |
System load regulation | ≤±0.5% | ||||
System voltage | ≤±0.5% | ||||
System stability | ≤±0.5% | ||||
Efficiency | ≥ 93.2% | ||||
Current sharing | module current sharing not more than ±5% | ||||
Weighted noise | ≤ 2mV (300Hz ~ 3400Hz) | ||||
Output distribution | MCB optional | ||||
Rectifier module unit | Rectifier hot-swap | Hot-swap available.not influencing system operation | |||
Rectifier indication | with operation.alarm.and fault indicators | ||||
Soft start time | 3s-10s | ||||
Installation method | support swappable | ||||
rectifier fault influence | Not influencing the set parameters of rectifier when rectifier at fault | ||||
Monitor module unit | Remote monitoring | With remote metering & remote control & remote signaling functions. providing standard RS485&TCP/IP Interface and 6 sets of the dry contact output port & Battery Temp.Sensor | |||
Language | Default: English | ||||
Remote control | rectifier start and close.battery test. equalize and float charging ,DIN /DO configuration and so on | ||||
Alarm functions | With AC over voltage/under voltage.DC voltage over/under.module Communication fault and over temperature alarm,Battery remove,Surge and so on | ||||
SAFTEY | Insulation resistance | Testing voltage 500VDC, Insulation Resistance ≥10M (normal atmospheric pressure, normal temperature, relative humidity <90%, no condensation) | |||
Insulation strength | Input to output: 3500VDC @1min&leak current ≤10mA Input to enclosures: 3500VDC @1min&leak current ≤10mA Output to enclosures:750VDC @1min&leak current ≤10mA |
||||
System leak current | ≤3.5mA(230Vac input) | ||||
Grounding performance requirements | The system with operating ground and protection ground.with clear mark.the resistance between the enclosures of distribution and all palpable metal components and grounding nut is not more than 0.1Ω | ||||
AC lightning protection | The equipment AC side can bear simulated lightning impulse Current of waveform 8/20μS and rated amplitude 40kA.(Optional) |
||||
Noise | ≤55dB (A) (measured at 1m distance from the equipment) | ||||
MTBF | ≥ 100000 hours |