No | Field | Details | |
1 | System | Rectifier brand | NASN |
2 | Dimension (W*D*H)mm for rectifier system | 57×53×20cm | |
3 | Weight | 15KG | |
4 | Cooling mode | Natural cooling | |
5 | Installation mode | Installed in 19-inch rack or inside the cabinet or OD rack mountable | |
6 | Cabling mode | Top inlet and top outlet | |
7 | Maintenance mode | Front maintenance | |
8 | Potential level | IP20 | |
9 | AC Distributor | Input mode | 85 ~ 300 Vrms |
10 | Phase | Single/Three phase input, single phase module input | |
11 | Input CB capacity | 1X40A/3P | |
12 | Input frequency | 50Hz ±3% | |
13 | SPD | 40kA (Class B/ Type 2) | |
14 | DC Distributor | Nominal system voltage | - 48 V |
15 | Output voltage | 42 ~ 58V DC, rated value: -54V DC | |
16 | Over voltage protection | 59V | |
17 | Battery CB breakers or Fuse | 2X125A | |
18 | DC contactor | 2 Level: Critical-1 & Non-critical-1 | |
19 | Load breakers (Non-critical-1, LLVD1) | 63Ax1, 32Ax2, 16Ax1 | |
20 | Load breakers (Critical-1, BLVD) | 32Ax2, 16Ax2 | |
21 | Front access MCB arrangement | All MCM must be front access | |
22 | Additional/Actual load breakers | Supplier will mention | |
23 | SPD | Class C/ Type 3 | |
24 | EMI (conducted) | EN 55022, Class A | |
25 | Rectifiers | Rectifier maximum capacity | 6 KW (Supplier will mention) |
26 | Sequential start-up/ system soft start | ||
27 | Redundancy and power capacity supervision | ||
28 | High efficiency>96% | ||
29 | Overload protection | ||
30 | Rectifier Module | Input voltage | 85VAC ~ 300VAC, rated 220VAC |
31 | Module rated power | 1.5KW/1.75KW/2.0 KW | |
32 | THD | <5% | |
33 | Rectifier module protection | Protection option must be enable by using Internal fuse or circuit breaker or self protection | |
34 | Rectifier module slot | 4 slots | |
35 | Load sharing | Load share must be enabled | |
36 | Working temperature | -50C ~ 700C | |
37 | Module dimension (W*D*H), mm | Supplier will mention | |
38 | Weight, Kg | Supplier will mention | |
39 | Power factor | >0.99 | |
40 | Module visual Indications during operation | Green: Normal, Yellow: Alarm and Red: Fault | |
41 | Rectifier module | Hot plugable/ hot-swappable | |
42 | Easy maintenance | All modules shall be easy installed, removed with safety locked | |
43 | Module restart function | Each modules shall be start automatically (During power failure and restore) with 60 sec delay. | |
44 | Module feature with automatic sleep/wake-up. | ||
45 | Battery | Battery charging function | The system must have different moods for charging like boost/equalization and float |
46 | Charging current limitation (0.01C to 1.0C) | ||
47 | Low voltage disconnection | ||
48 | Backup time supervision | ||
49 | Others | Alarm output | 8 dry contact |
50 | Communication port | RS485, SNMP | |
51 | Display mode | LCD | |
52 | Detects the voltage, current and frequency of the AC input | ||
53 | AC measurement (internal / external) | ||
54 | Mains failure/phase failure detection and alarming | ||
55 | Configurable event and data log | ||
56 | Environment | Operating temperature | -50ºC ~ 75ºC |
57 | Storage temperature | -50ºC ~ 75ºC | |
58 | Operating humidity | 5% ~ 95% RH (Non-condensing) | |
59 | Altitude | 0 ~ 3000 m | |
60 | Protection | Input overvoltage protection | Protection point: >300VAC |
61 | Input undervoltage protection | Protection point: <85VAC | |
62 | Output overvoltage protection | 58.5 ~ 60.5VDC or supplier will mention | |
63 | Over-temperature protection | Protection point: >75ºC | |
64 | Monitoring | Rectifier interface | Digital, CAN-based |
65 | Local monitoring | LAN / WEB browser | |
66 | Remote monitoring | LAN / modem, GSM, GPRS / WEB browser | |
67 | Remote alarming | Dry contacts / SNMP/SMS | |
68 | Languages | English | |
69 | Reliability | MTBF | ≥ 100000 hours |
70 | Energy savings option | Options for enable one or more rectifiers module in hibernation based on the actual load power. | |
71 | De-rating factors | De-rating tables and curves for electric power Rectifier System shall be supplied by the supplier under different ambient temperature, humidity and altitude. |