MODEL | B380/220-30M3 | B380/220-60M6 | B380/220-90M9 | B380/220-150M15 | B380/220-300M30 | |
Configuration | 3pcs 220V/10A module +1pcs monitor |
6pcs 220V/10A module +1pcs monitor |
9pcs 220V/10A module +1pcs monitor |
15pcs 220V/10A module +1pcs monitor |
30pcs 220V/20A module +1pcs monitor |
|
Environmental | Operating temperature | -40°C ~ 55°C | ||||
Storage temperature | -40°C ~ 70°C | |||||
Relative humidity | ≤ 90%RH (30°C) | |||||
Altitude | ≤ 2000m (derating is necessary above 2,000m) | |||||
AC Input | AC input system | L1+L2+L3+N/380Vac | ||||
Input voltage range | 323-437VAC | |||||
Input AC voltage frequency | 45Hz ~ 65Hz | |||||
Max input current | ≤28.4A | |||||
Power factor | ≥ 0.99 | |||||
DC Output | Nominal output voltage | 220VDC | ||||
Rated output voltage | 242VDC | |||||
Rated Output Capacity | 7.5kW | 15kW | 22.5kW | 37.5kW | 75kW | |
Output DC voltage | 180VDC ~ -300VDC | |||||
Output DC current | 30A | 60A | 90A | 150A | 300A | |
Voltage set-point accuracy | ≤ 1% | |||||
Efficiency | ≥ 93.2% | |||||
Noise (peak-peak) | ≤ 200mV (0 ~ 20MHz) | |||||
Weighted noise | ≤ 2mV (300Hz ~ 3400Hz) | |||||
AC Input Alarm and Protection | AC input over-voltage alarm point | Default: 280VAC ± 5VAC* | ||||
AC input under-voltage alarm point | Default: 176VAC ± 5VAC | |||||
AC input over-voltage protection recovery difference | Default: 295VAC ± 5VAC, 10VAC lower than the AC input over-voltage protection point | |||||
AC input under-voltage protection point | Default: 180VAC ± 5VAC* | |||||
DC Output Alarm And Protection | DC output over-voltage alarm point | Default:298VDC ± 0.5VDC* | ||||
DC output under-voltage alarm point | Default: 180VDC ± 0.5VDC* | |||||
DC output over-voltage protection point | Default: 194.5VDC ± 0.5VDC* | |||||
LLVD | Default: 198VDC ± 0.5VDC* | |||||
BLVD | Default: 194.5VDC ± 0.5VDC* | |||||
Rectifier | Load sharing | The rectifiers can work in parallel and share the current. The unbalance is better than ± 5% rated output current. | ||||
Derated by input (at 45°C) | The rectifier can output power of 100% with input voltage of ≥154VAC; The rectifier can output power capacity 1200W with input voltage <154VAC; Rectifiers under-voltage stop with input voltage of 85VAC |
|||||